누설 전류 모니터링에 의한 오손된 고분자 애자에서의 섬락 예지 방법
A Flashover Prediction Method by the Leakage Current Monitoring in the Contaminated Polymer Insulator

박재준   (중부대학교 전기전자공학과UU0001194  ); 송영철   (경북대학교 전자전기공학부UU0000096  );
  • 초록

    In this Paper, a flashover prediction method using the leakage current in the contaminated EPDM distribution polymer insulator is proposed. The leakage currents on the insulator were measured simultaneously with the different salt fog application such as 25g, 50g, and 75g per liter of deionized water. Then, the measured leakage currents were enveloped and transformed as the CDFS using the Hilbert transform and the level crossing rate, respectively. The obtained CDFS having different gradients(angles) were used as a important factor for the flashover prediction of the contaminated polymer insulator. Thus, the average angle change with an identical salt fog concentration was within a range of 20 degrees, and the average angle change among the different salt fog concentrations was 5 degrees. However, it is hard to be distinguished each other because the gradient differences among the CDFS were very small. So, the new weighting value was defined and used to solve this problem. Through simulation, it Is verified that the proposed method has the capability of the flashover prediction.


  • 주제어

    Flashover prediction .   Leakage current monitoring .   Hilbert transform .   Cumulative Density Function.  

  • 참고문헌 (5)

    1. G. Karady and F. Amarch, 'Signature analysis of leakage current for polluted insulators,' in Proc. IEEE Transmission and Distribution Conf., vol. 2, New Orleans, LA, Apr. 1999, pp. 806-811 
    2. S. O. Rice, 'Mathematical analysis of random noise,' Bell Syst, Tech. J., vol. 23, pp. 282-332, July 1994 
    3. A. Papoulis, Probability, Random Variable and Stochastic Processes, New York: McGraw-Hill, 1984 
    4. S. Braun and J. K. Hammond, 'Additional techniques,' in Mechanical Signature Analysis. London, U.K. : Academic, 1996 
    5. K. J. Lloyd and H. M. Schneider, 'Insulation for power frequency voltage,' in Transmission Line Reference Book (345 kV abd Above). Palo Alto, CA:EPRI, 1982 

 저자의 다른 논문

  • 박재준 (76)

    1. 1999 "회귀분석을 이용한 복합 시스템의 열화진단" 照明·電氣設備學會論文誌 = Journal of the Korean Institute of Illuminating and Electrical Installation Engineers 13 (1): 39~45    
    2. 1999 "신경회로망을 이용한 절연 열화진단에 관한 연구" 情報學硏究 = The studies of information technology 2 (2): 13~22    
    3. 2001 "이산웨이블렛 변환과 신경망을 이용한 변압기 열화상태 진단에 관한 연구" 전기전자재료학회논문지 = Journal of the Korean institute of electronic material engineers 14 (1): 84~92    
    4. 2001 "변압기 부분방전 상시 감시기법에 관한 연구" 전기전자재료학회논문지 = Journal of the Korean institute of electronic material engineers 14 (12): 1032~1040    
    5. 2003 "웨이블렛변환을 이용한 부분방전 종류의 특징추출에 관한 연구" 情報學硏究 = The studies of information technology 6 (1): 65~70    
    6. 2004 "고압전동기 고정자권선 결함 부분방전패턴" 情報學硏究 = The studies of information technology 7 (1): 155~161    
    7. 2004 "카올린으로 오손된 애자의 표면방전 및 방사전자파의 신호 분석" 情報學硏究 = The studies of information technology 7 (3): 113~118    
    8. 2004 "고압전동기 고정자권선의 부분방전 특징추출" 情報學硏究 = The studies of information technology 7 (4): 61~69    
    9. 2005 "Feature Extraction of Simulated fault Signals in Stator Windings of a High Voltage Motor and Classification of Faulty Signals" 전기전자재료학회논문지 = Journal of the Korean institute of electronic material engineers 18 (10): 965~975    
    10. 2006 "극초고주파용 CPW의 결합노이즈특성에 관한 연구" 전기전자재료학회논문지 = Journal of the Korean institute of electronic material engineers 19 (2): 158~161    

 활용도 분석

  • 상세보기

    amChart 영역
  • 원문보기

    amChart 영역

원문보기

무료다운로드
  • NDSL :
유료다운로드

유료 다운로드의 경우 해당 사이트의 정책에 따라 신규 회원가입, 로그인, 유료 구매 등이 필요할 수 있습니다. 해당 사이트에서 발생하는 귀하의 모든 정보활동은 NDSL의 서비스 정책과 무관합니다.

원문복사신청을 하시면, 일부 해외 인쇄학술지의 경우 외국학술지지원센터(FRIC)에서
무료 원문복사 서비스를 제공합니다.

NDSL에서는 해당 원문을 복사서비스하고 있습니다. 위의 원문복사신청 또는 장바구니 담기를 통하여 원문복사서비스 이용이 가능합니다.

이 논문과 함께 이용한 콘텐츠
이 논문과 함께 출판된 논문 + 더보기