2단 응축 히트펌프 온수시스템의 사이클 해석 및 성능분석
Performance of Heat Pump Water Heater with Dual Condenser

유영선   (National Institute of Agricultural EngineeringCC0187572  ); 김영중   (National Institute of Agricultural EngineeringCC0187572  ); 강금춘   (National Institute of Agricultural EngineeringCC0187572  ); 백이   (National Institute of Agricultural EngineeringCC0187572  ); 윤진하   (National Institute of Agricultural EngineeringCC0187572  ); 강연구   (National Institute of Agricultural EngineeringCC0187572  ); 이형모   (National Institute of Agricultural EngineeringCC0187572  );
  • 초록

    The heat pump water heater developed in this research consisted of one evaporator, one compressor, 1st condenser, 2nd condenser, one expansion valve, one water tank, one recirculation circuit and etc. The performance of heat pump water heater was tested and analyzed. The quantities of output water changed linearly from 2380 to $660{\ell}/h$ , and the output water temperature changed curvedly from 29.9 to $44.5^{\circ}C$ when the opening rate of recirculation valve changed from 0 to 100%. The COP of heat pump water heater increased from 3.0 to 3.8 when the quantities of output water changed from 660 to $2380{\ell}/h$ . When the temperature distributions of water tank were measured during 50 minutes after turning on the heat pump, the temperature stratification by the level appeared apparently. When the inlet water temperature changed from 30 to $50^{\circ}C$ , the output energy of heat pump hardly changed. The surface area of double pipe heat exchanger changed from 0.429 to $6.254m^2$ when the compressor capacity increased from 1.0 to 50.0 PS.


  • 주제어

    Heat pump .   Water heater .   Water tank.  

  • 참고문헌 (5)

    1. Gregory, S. B. 1999. Heat pump apparatus for heating liquid. United States Patent Number 5,984,198 
    2. Edwin, L. G. 1996. Heat pump hot water heater. United States Patent Number 5,573,192 
    3. Glen, P. R. 1996. Fast recovery circuit for heat pump water heater. United States Patent Number 5,495,551 
    4. Ryou, Y. S., Y. J. Kim, G. C. Kang, Y. Paek, J. H. Yun and G. J. Lee. 2001. Performance of an advanced heat pump water heater with pre-condenser. Proceedings of the KSAM 2001 Winter Conference 6(1): 117-123 
    5. John, T. D. 1999. Heat pump water heater and storage tank assembly. United States Patent Number 5,946,927 

 저자의 다른 논문

  • 강금춘 (2)

    1. 2006 "보온터널 난방을 위한 온수난방용 코일튜브 열교환기의 열전달 특성" 바이오시스템공학 = Journal of biosystems engineering 31 (5): 430~435    
    2. 2016 "온수배관을 이용한 시설딸기 부분난방기술 개발" 한국농공학회논문집 = Journal of the Korean Society of Agricultural Engineers 58 (5): 71~79    

 활용도 분석

  • 상세보기

    amChart 영역
  • 원문보기

    amChart 영역

원문보기

무료다운로드
  • NDSL :
  • 한국농업기계학회 : 저널
유료다운로드

유료 다운로드의 경우 해당 사이트의 정책에 따라 신규 회원가입, 로그인, 유료 구매 등이 필요할 수 있습니다. 해당 사이트에서 발생하는 귀하의 모든 정보활동은 NDSL의 서비스 정책과 무관합니다.

원문복사신청을 하시면, 일부 해외 인쇄학술지의 경우 외국학술지지원센터(FRIC)에서
무료 원문복사 서비스를 제공합니다.

NDSL에서는 해당 원문을 복사서비스하고 있습니다. 위의 원문복사신청 또는 장바구니 담기를 통하여 원문복사서비스 이용이 가능합니다.

이 논문과 함께 출판된 논문 + 더보기